NR 440.28(5)(c)2.
2. An engineering evaluation that the administrator determines is an accurate method of determining equivalence.
NR 440.28(5)(d)
(d) The administrator may condition the permission on requirements that may be necessary to ensure operation and maintenance to achieve the same emissions reduction as specified in
sub. (3).
NR 440.28(5)(e)
(e) The primary vapor-mounted seal in the “Volume-Maximizing Seal" manufactured by R.F.I. Services Corporation is approved as equivalent to the vapor-mounted seal required by
sub. (3) (a) 1. a. and shall meet the gap criteria specified in
sub. (3) (a) 1. a. 2). There may be no gaps between the tank wall and any secondary seal used in conjunction with the primary seal in the “Volume-Maximizing Seal."
NR 440.28(6)(a)(a) Except as provided in
par. (d), the owner or operator subject to this section shall maintain a record of the petroleum liquid stored, the period of storage, and the maximum true vapor pressure of that liquid during the respective storage period.
NR 440.28(6)(b)
(b) Available data on the typical Reid vapor pressure and the maximum expected storage temperature of the stored product may be used to determine the maximum true vapor pressure from nomographs contained in API Publication 2517, incorporated by reference in
s. NR 440.17, unless the department specifically requests that the liquid be sampled, the actual storage temperature determined, and the Reid vapor pressure determined from samples.
NR 440.28(6)(c)
(c) The true vapor pressure of each type of crude oil with a Reid vapor pressure less than 13.8 kPa (2.0 psia) or whose physical properties preclude determination by the recommended method shall be determined from available data and recorded if the estimated true vapor pressure is greater than 6.9 kPa (1.0 psia).
NR 440.28(6)(d)
(d) The following are exempt from the requirements of this subsection:
NR 440.28(6)(d)1.
1. Each owner or operator of each storage vessel storing a petroleum liquid with a Reid vapor pressure of less than 6.9 kPa (1.0 psia) provided the maximum true vapor pressure does not exceed 6.9 kPa (1.0 psia).
NR 440.28(6)(d)2.
2. Each owner or operator of each storage vessel equipped with a vapor recovery and return or disposal system in accordance with the requirements of
sub. (3) (a) 3. and
(b), or a closed vent system and control device meeting the specifications of
40 CFR 65.42 (b) (4), (5) or (c), as in effect on December 14, 2000.
NR 440.28 History
History: Cr.
Register, January, 1984, No. 337, eff. 2-1-84; am. (2) (intro.), (h), (4) (a) 1. a. intro., r. (5) (a) and (b), renum. (5) (c) to (e), cr. (4) (a) 1. a. 4) and 5), (5) (a) to (d),
Register, September, 1990, No. 417, eff. 10-1-90; am. (2) (j) and (6) (b),
Register, July, 1993, No. 451, eff. 8-1-93;
CR 06-109: am. (1) (a), (2) (f), (h), (6) (d) 2., cr. (1) (c) Register May 2008 No. 629, eff. 6-1-08; correction in (1) (c) 1. made under s. 13.92 (4) (b) 7., Stats., Register May 2008 No. 629. NR 440.285
NR 440.285 Volatile organic liquid storage vessels (including petroleum liquid storage vessels) for which construction, reconstruction or modification commenced after July 23, 1984. NR 440.285(1)
(1)
Applicability and designation of affected facility. NR 440.285(1)(a)(a) Except as provided in
pars. (b) to
(d), the affected facility to which this section applies is each storage vessel with a capacity greater than or equal to 75 cubic meters (m
3) that is used to store volatile organic liquids (VOL) for which construction, reconstruction or modification is commenced after July 23, 1984.
NR 440.285(1)(b)
(b) This section does not apply to storage vessels with a capacity greater than or equal to 151 m
3 storing a liquid with a maximum true vapor pressure less than 3.5 kilopascals (kPa) or with a capacity greater than or equal to 75 m
3 but less than 151 m
3 storing a liquid with a maximum true vapor pressure less than 15.0 kPa.
NR 440.285(1)(d)2.
2. Pressure vessels designed to operate in excess of 204.9 kPa and without emissions to the atmosphere.
NR 440.285(1)(d)3.
3. Vessels permanently attached to mobile vehicles such as trucks, railcars, barges or ships.
NR 440.285(1)(d)4.
4. Vessels with a design capacity less than or equal to 1,589.874 m
3 used for petroleum or condensate stored, processed, or treated prior to custody transfer.
NR 440.285(1)(e)1.1. Owners or operators may choose to comply with
40 CFR part 65, subpart C, as in effect on December 14, 2000, to satisfy the requirement of
subs. (3) to
(7) for storage vessels that are subject to this section and meet either of the specifications in this subdivision. When choosing to comply with
40 CFR part 65, subpart C, the monitoring requirements of
sub. (7) (c),
(e),
(f) 1. and
(g) shall apply. Other provisions applying to owners or operators who choose to comply with
40 CFR part 65 are provided in
40 CFR 65.1. The specifications are that the storage vessel has either of the following:
NR 440.285(1)(e)1.a.
a. A design capacity greater than or equal to 151 m
3 and containing a VOL that, as stored, has a maximum true vapor pressure equal to or greater than 5.2 kPa.
NR 440.285(1)(e)1.b.
b. A design capacity greater than 75 m
3 but less than 151 m
3 and containing a VOL that, as stored, has a maximum true vapor pressure equal to greater than 27.6 kPa.
NR 440.285(1)(e)2.
2. Owners or operators who choose to comply with
40 CFR part 65, subpart C, as in effect on December 14, 2000, shall also comply with
ss. NR 440.01,
440.02,
440.05,
440.06,
440.07 (1) (a) and
(d),
440.14 and
440.15 for those storage vessels. Any section or subsection from
ss. NR 440.01 to
440.19 not specified in this subdivision does not apply to owners or operators of storage vessels complying with
40 CFR part 65, subpart C, except that provisions required to be met prior to implementing
40 CFR part 65 still apply. Owners and operators who choose to comply with
40 CFR part 65, subpart C, shall comply with
40 CFR part 65, subpart A, as in effect on December 14, 2000.
NR 440.285(1)(e)3.
3. If an owner or operator installs an internal floating roof and, at initial startup, chooses to comply with
40 CFR part 65, subpart C, as in effect on December 14, 2000, a report shall be furnished to the department stating that the control equipment meets the specifications of
40 CFR 65.43 as in effect on December 14, 2000. This report shall be an attachment to the notification required by
40 CFR 65.5 (b) as in effect on December 14, 2000.
NR 440.285(1)(e)4.
4. If an owner or operator installs an external floating roof and, at initial startup, chooses to comply with
40 CFR part 65, subpart C, as in effect on December 14, 2000, a report shall be furnished to the department stating that the control equipment meets the specifications of
40 CFR 65.44 as in effect on December 14, 2000. This report shall be an attachment to the notification required by
40 CFR 65.5 (b) as in effect on December 14, 2000.
NR 440.285(2)
(2) Definitions. As used in this section, terms not defined in this subsection have the meanings given in
s. NR 440.02.
NR 440.285(2)(a)
(a) “Bulk gasoline plant" means any gasoline distribution facility that has a gasoline throughput less than or equal to 75,700 liters per day. Gasoline throughput shall be the maximum calculated design throughput as may be limited by compliance with an enforceable condition under federal requirements or federal, state, or local law, and discoverable by the department and any other person.
NR 440.285(2)(b)
(b) “Condensate" means hydrocarbon liquid separated from natural gas that condenses due to changes in the temperature or pressure, or both, and remains liquid at standard conditions.
NR 440.285(2)(c)
(c) “Custody transfer" means the transfer of produced petroleum or condensate, after processing or treatment in the producing operations, from storage vessels or automatic transfer facilities to pipelines or any other forms of transportation.
NR 440.285(2)(d)
(d) “Fill" means the introduction of VOL into a storage vessel but not necessarily to complete capacity.
NR 440.285(2)(e)
(e) “Gasoline service station" means a site where gasoline is dispensed to motor vehicle fuel tanks from stationary storage tanks.
NR 440.285(2)(f)
(f) “Maximum true vapor pressure" means the equilibrium partial pressure exerted by the volatile organic compounds (as defined in
40 CFR 51.100) in the stored VOL at the temperature equal to the highest calendar-month average of the VOL storage temperature for VOLs stored above or below the ambient temperature or at the local maximum monthly average temperature as reported by the national weather service for VOLs stored at the ambient temperature, as determined in one of the following ways:
NR 440.285(2)(f)1.
1. In accordance with the method described in American Petroleum Institute Publication 2517, Evaporation Loss From External Floating Roof Tanks, incorporated by reference in
s. NR 440.17 (2) (c) 1.
NR 440.285(2)(g)
(g) “Petroleum" means the crude oil removed from the earth and the oils derived from tar sands, shale and coal.
NR 440.285(2)(h)
(h) “Petroleum liquids" means petroleum, condensate, and any finished or intermediate products manufactured in a petroleum refinery.
NR 440.285(2)(hm)
(hm) “Process tank" means a tank that is used within a process, including a solvent or raw material recovery process, to collect material discharged from a feedstock storage vessel or equipment within the process before the material is transferred to other equipment within the process, to a product or by-product storage vessel, or to a vessel used to store recovered solvent or raw material. In many process tanks, unit operations such as reactions and blending are conducted. Other process tanks, such as surge control vessels and bottoms receivers, however, may not involve unit operations.
NR 440.285(2)(i)
(i) “Reid vapor pressure" means the absolute vapor pressure of volatile crude oil and volatile nonviscous petroleum liquids except liquified petroleum gases, as determined by ASTM D323-94, incorporated by reference in
s. NR 440.17 (2) (a) 11.
NR 440.285(2)(j)
(j) “Storage vessel" means each tank, reservoir, or container used for the storage of volatile organic liquids but does not include any of the following:
NR 440.285(2)(j)1.
1. Frames, housing, auxiliary supports, or other components that are not directly involved in the containment of liquids or vapors.
NR 440.285(2)(k)
(k) “Volatile organic liquid" or “VOL" means any organic liquid which can emit volatile organic compounds, as defined in
40 CFR 51.100, into the atmosphere.
NR 440.285(2)(L)
(L) “Waste" means any liquid resulting from industrial, commercial, mining or agricultural operations, or from community activities that is discarded or is being accumulated, stored, or physically, chemically, or biologically treated prior to being discarded or recycled.
NR 440.285(3)(a)(a) The owner or operator of each storage vessel with a design capacity greater than or equal to 151 m
3 containing a VOL that, as stored, has a maximum true vapor pressure equal to or greater than 5.2 kPa but less than 76.6 kPa, or with a design capacity greater than or equal to 75 m
3 but less than 151 m
3 containing a VOL that, as stored, has a maximum true vapor pressure equal to or greater than 27.6 kPa but less than 76.6 kPa, shall equip each storage vessel with one of the following:
NR 440.285(3)(a)1.
1. A fixed roof in combination with an internal floating roof meeting the following specifications:
NR 440.285(3)(a)1.a.
a. The internal floating roof shall rest or float on the liquid surface (but not necessarily in complete contact with it) inside a storage vessel that has a fixed roof. The internal floating roof shall be floating on the liquid surface at all times, except during initial fill and during those intervals when the storage vessel is completely emptied or subsequently emptied and refilled. When the roof is resting on the leg supports, the process of filling, emptying, or refilling shall be continuous and shall be accomplished as rapidly as possible.
NR 440.285(3)(a)1.b.
b. Each internal floating roof shall be equipped with one of the following closure devices between the wall of the storage vessel and the edge of the internal floating roof:
1) A foam- or liquid-filled seal mounted in contact with the liquid (liquid-mounted seal). A liquid-mounted seal means a foam- or liquid-filled seal mounted in contact with the liquid between the wall of the storage vessel and the floating roof continuously around the circumference of the storage vessel.
2) Two seals mounted one above the other so that each forms a continuous closure that completely covers the space between the wall of the storage vessel and the edge of the internal floating roof. The lower seal may be vapor-mounted, but both must be continuous.
3) A mechanical shoe seal. A mechanical shoe seal is a metal sheet held vertically against the wall of the storage vessel by springs or weighted levers and is connected by braces to the floating roof. A flexible coated fabric (envelope) spans the annular space between the metal sheet and the floating roof.
NR 440.285(3)(a)1.c.
c. Each opening in a noncontact internal floating roof except for automatic bleeder vents (vacuum break vents) and the rim space vents is to provide a projection below the liquid surface.
NR 440.285(3)(a)1.d.
d. Each opening in the internal floating roof except for leg sleeves, automatic bleeder vents, rim space vents, column wells, ladder wells, sample wells and stub drains is to be equipped with a cover or lid which is to be maintained in a closed position at all times (i.e., no visible gap) except when the device is in actual use. The cover or lid shall be equipped with a gasket. Covers on each access hatch and automatic gauge float well shall be bolted except when they are in use.
NR 440.285(3)(a)1.e.
e. Automatic bleeder vents shall be equipped with a gasket and are to be closed at all times when the roof is floating except when the roof is being floated off or is being landed on the roof leg supports.
NR 440.285(3)(a)1.f.
f. Rim space vents shall be equipped with a gasket and are to be set to open only when the internal floating roof is not floating or at the manufacturer's recommended setting.
NR 440.285(3)(a)1.g.
g. Each penetration of the internal floating roof for the purpose of sampling shall be a sample well. The sample well shall have a slit fabric cover that covers at least 90% of the opening.
NR 440.285(3)(a)1.h.
h. Each penetration of the internal floating roof that allows for passage of a column supporting the fixed roof shall have a flexible fabric sleeve seal or a gasketed sliding cover.
NR 440.285(3)(a)1.i.
i. Each penetration of the internal floating roof that allows for passage of a ladder shall have a gasketed sliding cover.
NR 440.285(3)(a)2.
2. An external floating roof. An external floating roof means a pontoon-type or double-deck type cover that rests on the liquid surface in a vessel with no fixed roof. Each external floating roof shall meet the following specifications:
NR 440.285(3)(a)2.a.
a. Each external floating roof shall be equipped with a closure device between the wall of the storage vessel and the roof edge. The closure device is to consist of 2 seals, one above the other. The lower seal is referred to as the primary seal, and the upper seal is referred to as the secondary seal.
1) The primary seal shall be either a mechanical shoe seal or a liquid-mounted seal. Except as provided in sub. (4) (b) 4., the seal shall completely cover the annular space between the edge of the floating roof and storage vessel wall.
2) The secondary seal shall completely cover the annular space between the external floating roof and the wall of the storage vessel in a continuous fashion except as allowed in sub. (4) (b) 4.
NR 440.285(3)(a)2.b.
b. Except for automatic bleeder vents and rim space vents, each opening in a noncontact external floating roof shall provide a projection below the liquid surface. Except for automatic bleeder vents, rim space vents, roof drains, and leg sleeves, each opening in the roof is to be equipped with a gasketed cover, seal, or lid that is to be maintained in a closed position at all times (i.e., no visible gap) except when the device is in actual use. Automatic bleeder vents are to be closed at all times when the roof is floating except when the roof is being floated off or is being landed on the roof leg supports. Rim vents are to be set to open when the roof is being floated off the roof leg supports or at the manufacturer's recommended setting. Automatic bleeder vents and rim space vents are to be gasketed. Each emergency roof drain is to be provided with a slotted membrane fabric cover that covers at least 90% of the area of the opening.
NR 440.285(3)(a)2.c.
c. The roof shall be floating on the liquid at all times (i.e., off the roof leg supports) except during initial fill until the roof is lifted off leg supports and when the storage vessel is completely emptied and subsequently refilled. The process of filling, emptying, or refilling when the roof is resting on the leg supports shall be continuous and shall be accomplished as rapidly as possible.
NR 440.285(3)(a)3.
3. A closed vent system and control device meeting the following specifications:
NR 440.285(3)(a)3.a.
a. The closed vent system shall be designed to collect all VOC vapors and gases discharged from the storage vessel and operated with no detectable emissions as indicated by an instrument reading of less than 500 ppm above background and visual inspections, as determined in
s. NR 440.62 (6) (b).
NR 440.285(3)(a)3.b.
b. The control device shall be designed and operated to reduce inlet VOC emissions by 95% or greater. If a flare is used as the control device, it shall meet the specifications described in the general control device requirements under
s. NR 440.18.
NR 440.285(3)(b)
(b) The owner or operator of each storage vessel with a design capacity greater than or equal to 75 m
3 which contains a VOL that, as stored, has a maximum true vapor pressure greater than or equal to 76.6 kPa shall equip each storage vessel with one of the following:
NR 440.285(4)
(4) Testing and procedures. The owner or operator of each storage vessel as specified in
sub. (3) (a) shall meet the requirements of
par. (a),
(b), or
(c). The applicable paragraph for a particular storage vessel depends on the control equipment installed to meet the requirements of
sub. (3).
NR 440.285(4)(a)
(a) After installing the control equipment required to meet
sub. (3) (a) 1. (permanently affixed roof and internal floating roof), each owner or operator shall:
NR 440.285(4)(a)1.
1. Visually inspect the internal floating roof, the primary seal, and the secondary seal (if one is in service), prior to filling the storage vessel with VOL. If there are holes, tears or other openings in the primary seal, the secondary seal, or the seal fabric or defects in the internal floating roof, or both, the owner or operator shall repair the items before filling the storage vessel.
NR 440.285(4)(a)2.
2. For vessels equipped with a liquid-mounted or mechanical shoe primary seal, visually inspect the internal floating roof and the primary seal or the secondary seal (if one is in service) through manholes and roof hatches on the fixed roof at least once every 12 months after initial fill. If the internal floating roof is not resting on the surface of the VOL inside the storage vessel, or there is liquid accumulated on the roof, or the seal is detached, or there are holes or tears in the seal fabric, the owner or operator shall repair the items or empty and remove the storage vessel from service within 45 days. If a failure that is detected during inspections required under this paragraph cannot be repaired within 45 days and if the vessel cannot be emptied within 45 days, a 30-day extension may be requested from the department in the inspection report required in
sub. (6) (a) 3. A request for an extension shall document that alternate storage capacity is unavailable and specify a schedule of actions the company owner or operator shall take to assure that the control equipment will be repaired or the vessel will be emptied as soon as possible.
NR 440.285(4)(a)4.
4. Visually inspect the internal floating roof, the primary seal, the secondary seal (if one is in service), gaskets, slotted membranes (if any), and sleeve seals (if any) each time the storage vessel is emptied and degassed. If the internal floating roof has defects, the primary seal has holes, tears or other openings in the seal or the seal fabric, the secondary seal has holes, tears or other openings in the seal or the seal fabric, the gaskets no longer close off the liquid surfaces from the atmosphere, or the slotted membrane has more than 10% open area, the owner or operator shall repair the items as necessary so that none of the conditions specified in this paragraph exist before refilling the storage vessel with VOL. In no event may inspections conducted in accordance with this provision occur at intervals greater than 10 years in the case of vessels undergoing annual visual inspections as specified in
subds. 2. and
3. b. nor at intervals greater than 5 years in the case of vessels specified in
subd. 3. a.
NR 440.285(4)(a)5.
5. Notify the department in writing at least 30 days prior to the filling or refilling of each storage vessel for which an inspection is required by
subds. 1. and
4. to afford the department the opportunity to have an observer present. If the inspection required by
subd. 4. is not planned and the owner or operator could not have known about the inspection 30 days in advance of refilling the storage vessel, the owner or operator shall notify the department at least 7 days prior to the refilling of the storage vessel. Notification shall be made by telephone immediately followed by written documentation demonstrating why the inspection was unplanned. Alternatively, this notification including the written documentation may be made in writing and sent by express mail so that it is received by the department at least 7 days prior to the refilling.